The SRV2S stainless steel direct-acting pressure reducing valve is compact and suitable for steam or gas systems such as compressed air. All parts in contact with the medium are made of stainless steel.
| Limitations (Stainless Steel) | ● Design pressure (PMA): 25 bar ● Maximum operating pressure (PMO): 19 bar ● Maximum operating temperature (TMO): 212℃ |
| Installation Instructions | Please install the pressure reducing valve on a horizontal pipe following the direction of the arrow on the valve body. |
| Bill of Materials | ● Valve body and cover: CF8, CF3M ● Valve seat: F304, F316L ● Valve core: SUS440C ● Bellows: 316Ti ● Pressure regulating spring: Silicon-chromium spring steel |
| Downstream Pressure Range | There are three different downstream pressure setting ranges, distinguished by color on the handwheel’s color indicator: ● Gray downstream pressure range: 0.14 bar – 1.7 bar ● Green downstream pressure range: 1.4 bar – 4.0 bar ● Orange downstream pressure range: 3.5 bar – 8.6 bar |
Dimensions/weight (approximately) mm and kg
| Model | SRV25 | |||
| Nominal diameter | 15 | 20 | 25 | |
| A(mm) | 83 | 96 | 108 | |
| B(mm)ANSI 150 | 140 | 153 | ||
| B(mm)Pn25 | 150 | 160 | ||
| C(mm) | 62 | |||
| D(mm) | 130 | |||
| E(mm) | 25 | |||
| Weight (Kg) | Thread | 1.6 | 1.7 | 1.8 |
| Flange | 3.2 | 4 | 4.5 | |
Displacement is used for safety valve selection.
Full-open flow rate is used for safety valve selection.
| Caliber | DN15 | DN20 | DN25 |
| Cv | 1.5 | 2.5 | 3 |
Conversion formulas: Cv(UK) = Kv x 0.963 Cv(US) = Kv x 1.156
Saturated steam and compressed air selection
How to use the selection chart
The curves labeled 2, 3, 4, 5, etc. represent upstream pressure, and the vertical line on the left side of the figure represents downstream pressure.
Example description
The pressure reducing valve requires a flow rate of 120 kg/h, with the pressure decreasing from 8 barg to 6 barg. Moving horizontally to the right along the downstream pressure (6 barg) curve shown on the left side of the diagram, until it intersects with the upstream pressure (8 barg) curve, and then vertically downwards along the intersection point, it can be seen that SRV2S meets the requirements.